Beckett furnace manual




















On by mod - What to do about abnormally high hot water heating boiler pressure. Rhonda What to do about abnormally high hot water heating boiler pressure Watch out : excessive boiler pressure in a residential hot water heating system is dangerous, risking a BLEVE explosion search InspectApedia.

If your heating boiler pressure really is over 30 PSI and your relief valve is not opening, then the heating system is unsafe. We need more information: you need to be more clear with me about what pressure or "psi" we're actually discussing.

Where are you reading "high psi"? If your boiler pressure were really over 30 psi, I don't think it would have been possible to replace a relief valve and an expansion tank without water pouring out at the connections for those devices.

That would have relieved the pressure. So if pressure was relieved in the hot water hydronic heating system boiler, piping, etc. So, what is "High" and where and how are you determining that? My Beckett boiler psi stuck on high, replaced relief valve, expansion tank, how do I release the psi pressure, furnace does not fire up.

It would help me research to try to find manuals for your heater if you would post a photo of the heater and in additional comments photos of any logos or data tags you can find on the equipment. I'm looking for a universal constant level flow control system for my seigler oil stove.

A repair manual would be good. I can't find part numbers. Cf burner manual cf burner manual cf burner manual cf burner manual cg10 burner manual cg10 24 burner manual cg15 25 50 burner manual.

Do not use chassis ground system. It reveals the elements of the circuit as streamlined shapes as well as the power as well as signal links in between the gadgets. A wiring diagram is a streamlined traditional photographic representation of an electric circuit. Beckett burner wire diagram wiring diagram beckett oil burner wiring diagram. Hard wire burner ground to battery. Elyria ohio r w beckett corp. Beckett oil burner wiring diagram you will need an extensive expert and easy to know wiring diagram.

If the flame light remains on, replace the GeniSys Primary Control. If the light goes off, replace the cad cell part number U. A flame during purge cycles. Too many recycle attempts. An ideal flame signal is Ohms or less. Additional Actions: Hold the reset button down for 15 seconds. Cause 1 — Flame is present but sensor has weak or intermittent signal Action: Check and correct flame sensing circuit cad cell and wiring.

Cause 2 — Burner setup out of recommended adjustments Action: Verify burner specs. Cause 3 — Flame failure Action: Check and correct: Fuel supply.

Proper flue draft and chamber draft. Nozzle and air settings. See if a low firing rate baffle is required for this burner combination. Verify electrode condition and settings Notes: Refer to our Residential Oil Specification Guide to see start up settings. Cause 4 — Lack of retention Action: Check chamber. Draft oil supply, 3 nozzle spec. Cause 2 — Oil expansion in the nozzle line assembly, due to radiated heat at shutdown Action: Lower the CO2 by increasing air settings.

Put a post purge on control to remove excess heat. If greater, possible causes are: Excess air Improper CO2 as recommended by the appliance manufacturer Check the appliance manual for recommended CO2 Heat exchanger leaks Insufficient combustion air supply Action: Check and correct: Blocked flue, heat exchanger and chimney.

Burner head and nozzle combination. Insertion depth in short furnaces. Flame impingement on damaged refractory. High draft pulling partially burned products from the base of the flame.

Cold furnace. Greatly oversized furnace. Cause 1 — Not enough combustion air Action: Check and correct: Adequate combustion air to support all equipment. Debris obstructing air shutter and band. Correct air guide or inlet. Blower wheel not tight on motor shaft, correct blower wheel adjustment. Combustion air leakage from burner.

High furnace pressure. Cause 2 — Fouled Nozzle Action: Replace nozzle. Cause 3 — Air in oil supply Action: Run a vacuum test, Use a clear hose on the pump bleeder port to see if there is air present. Cause 4 — Wrong burner specifications Action: Refer to the Appliance manual. Cause 5 — Plugged heat exchanger Action: Check chamber and breech draft. Notes: Refer to the Appliance manufacturer for recommended draft settings.

Cause 6 — Fuel Quality Action: Test with alternate source of fuel. Cause 7 — Cracked heat exchanger Action: Replace chamber. Cause 8 — Flame impingement Action: Check nozzle, draft and combustion chamber. Cause 9 — Head and nozzle not correctly paired Action: Verify your components are correct. Cause 1 — Air in the pump Action: Check for air in the fuel supply line. Bleed the oil pump. Notes: For additional potential causes Click Here. Check for warpage or damage to blower wheel.

Make sure the motor is seated properly on the housing. Make sure motor bolts are evenly tightened. Check for debris in burner housing. Check the fit of the motor to housing and for potential damage to the housing.

Check shaft alignment. Make sure the coupling is not too tight. Notes: Refer to the burner manual for the proper gap of the blower to motor flange surface. Notes: RM Display Module is available for more in depth troubleshooting codes.

Cause 2 — CG15, CG25 and CG Power to motor but no power to control Action: Wire the control as shown on the schematic v control power is generally separate from high voltage motor power. Cause 3 — Control circuit fuse blown Action: Replace fuse. Cause 4 — Flame safeguard is defective Action: Verify the control is receiving voltage.

Notes: Replace flame safeguard. Cause 1 — Limit string not completed Action: Trace limit string with multimeter and correct. Notes: Verify there is v to terminals L2 and 6 on the subbase of the control.

Cause 2 — Blower motor is defective Action: Check and correct blower motor condition. Cause 3 — Flame safeguard is defective Action: Replace flame safeguard. Cause 1 — One of the configuration jumpers has been changed after hours of operation Action: Replace flame safeguard. Cause 2 — No power to blower motor Action 1 — CG10 Burner Models: When the limit string is complete, v is sent from terminal 5 of the controller subbase to the blower motor.

If voltage is present: Verify wiring to the motor is correct. Make sure the motor spins freely. The CG10 replacement part number is U. If voltage is present: Verify wiring to the motor contactor is correct. If the motor contactor is operating correctly, make sure the motor spins freely. Notes: Is JR3 intact? Cause 3 — Power to ignition or fuel valve circuits before completion of purge Action: Check and correct ignition and fuel valve wiring, re-set flame safeguard.

Action: Check furnace for flame or stray UV source bright light or spark — correct and re-set flame safeguard. Cause 6 — Flame safeguard purge card is defective or missing Action: Replace purge card, re-set flame safeguard.

Cause 10 — Flame safeguard is defective Action: Replace flame safeguard. Notes: Is jumper JR3 Intact? Notes: This is located on the top of the Control. Cause 1 — Fault in ignition circuit or a weak spark Action: Check and correct ignition transformer, high tension wire, electrode settings, flame safeguard ignition circuit and wiring. Notes: The flame establishing period is 4 seconds.

Cause 2 — Inadequate fuel supply to burner Action: Check and correct manual and electric valves in gas train, gas supply to train. Cause 3 — Flame detected during purge Action: Check furnace for flame or stray UV source bright light or spark — correct.

Cause 4 — Flame not detected within 4 seconds of energizing fuel valves Action: Observe the furnace for flame. Notes: Observe the furnace for flame. Cause 5 — Power to ignition or fuel valve circuits before completion of purge Action: Check and correct ignition and fuel valve wiring. Action: Check and correct damper travel is unobstructed, damper motor end switch setting, wiring. Action: Check and correct damper motor end switch wiring.

Cause 11 — Flame safeguard is defective Action: Replace flame safeguard. Cause 1 — Flame is present but sensor has weak or intermittent signal Action: Check and correct flame sensing circuit — flame rod or scanner, amplifier and wiring. Cause 2 — Flame failure Action: Check and correct fuel supply, air damper settings, blower wheel and motor, furnace draft Notes: Refer to our Commercial Gas Specification Guide to see start up settings.

Cause 3 — Low voltage for less than 4 minutes Action: Check and correct power supply to burner. Cause 1 — Low voltage for more than 4 minutes Action: Check and correct power supply to burner, re-set flame safeguard. Cause 2 — Power to ignition circuit during run interval Action: Check and correct ignition wiring, re-set flame safeguard. Cause 3 — Flame safeguard purge card is defective or missing Action: Replace purge card, re-set flame safeguard. If so, check and correct: Flame sensing circuit — flame rod or uv scanner.

Otherwise control recycles on flame failure. If so check and correct: Flame sensing circuit — flame rod or uv scanner. Cause 7 — RML low fire switch open during main flame establishing period Action: Check and correct air damper motor low fire switch and wiring, and air damper obstruction.

Cause 8 — Flame safeguard is defective Action: Replace flame safeguard. Cause 2 — Power to ignition or fuel valve circuits during postpurge Action: Check and correct: ignition and fuel valve wiring, re-set flame safeguard. Cause 1 — Boiler rate control wiring is in open position, preventing high fire Action: Trace power through rate control wiring to determine where power is lost — flame safeguard terminal — burner low fire switch — boiler rate control switch es — low air relay — correct as required to power damper motor.

Cause 2 — Damper motor is powered but will not move Action: Check for binding in damper — replace damper motor if required. Cause 3 — Flame safeguard terminal is not powered Action: Verify correct wiring, replace flame safeguard. Cause 1 — High fire fuel valve is not being powered Action: Trace power through fuel valve wiring to determine where power is lost — from flame safeguard to damper motor — damper motor switch — fuel valve wiring — correct as required to power fuel valve.

Cause 1 — Rubbing noise from blower wheel Action: Check and correct: wheel set screw tightness, wheel-to-motor plate and wheel-to-inlet guide clearances, wheel integrity. Cause 2 — Air in-rush noise at damper Action: Check and correct: damper obstructions, damper blade tightness on shaft, low fire firing rate too low causes noise.

Cause 3 — Harsh combustion noise Action: Check and correct: firing rate too high causes noise , O2 level excessive air causes noise , head setting adjustment. Cause 2 — Sharp pungent odor, burns eyes — aldehydes formed with carbon monoxide Action: Take corrective action gradually to avoid explosion hazard.

Cause 1 — Blower or motor imbalance burner shakes whenever blower runs Action: Check that blower is tight on motor shaft, has no missing balance weights, no obvious damage to blower wheel.

Cause 2 — Combustion pulsation burner shakes when burner is firing Action: Check and correct: excess air level, head setting, gas spud obstruction, correct blower wheel size, supply pressure to gas train high or very low pressure drop across regulator , pressure fluctuations coming to gas train from oversized supply regulator, pressure fluctuations coming to furnace from flue stack add a barometric , un-approved boiler application furnace too small.

Cause 1 — Flame size — too big Action: Check and correct: excess air is low low O2 or high CO2 , rate is high, operation at high elevation flame expands in low barometric pressure , flue gas recirculation, cold furnace. Cause 2 — Flame size — too small Action: Check and correct: excess air is high high O2 or low CO2 , rate is low, furnace has a lot of refractory re-radiated heat speeds up flame and shrinks its size.

Cause 3 — Lopsided flame — not centered in furnace Action: Check and correct: burner head not centered in air tube, gas orifice obstructed, furnace flow pattern flame drawn toward furnace outlet , furnace refractory pattern re-radiated heat from refractory speeds up flame , flame buoyancy in furnace greater influence in cold furnace.

Cause 4 — Flame color — too yellow Action: Always use properly calibrated instruments to set combustion. Cause 5 — Flame color — reddish blue Action: Always use properly calibrated instruments to set combustion. Cause 4 — O2 CO2 — outside specified range during modulation Action: The burner manual has a section devoted to modulation adjustments — work from it. Cause 1 — Not enough gas pressure to make rate high O2 at high fire Action: Check and correct: incoming gas pressure at rate, full open position on all manual valves, pressure drop across each SSOV, debris in gas line.

Cause 2 — Not enough air to make rate low O2 at high fire Action: Check and correct: adequate ventilation to support all boiler room equipment, high furnace pressure, burner head setting, full opening of burner air damper, debris obstructing air damper, correct air guide or inlet sleeve, blower wheel not tight on motor shaft, correct blower wheel adjustment, combustion air leakage from burner, scroll extension in place in CG10, correct 3 phase motor rotation, blower wheel damage.

Cause 1 — Low rate regulator un-adjusted Action: Clock firing rate and adjust gas pressure regulator for higher pressure. Cause 4 — Incorrect or defective burner head Action: Check burner head identification and orifice sizes.